Level Indicator: Utilizes the capacitance formed between the sensing
probe and the metallic vessel wall. A high frequency sine-wave is
applied between the probe and the vessel wall.
A change of the medium level will induce a change in the current of the applied sine wave.
From
Z=1/2pfc, when the capacitance in the vessel increase, impedance will
decrease and current will increase. Vice-versa, when the capacitance in
the vessel is small, the impedance will increase and current will
decrease accordingly.
-
Suitable for high temperature, high pressure and corrosive environment.
-
Not affected by noisy, dusty, misty and changes in the temperature.
-
No blind distance, ideal for different tanks.
-
Economic for large tanks
-
4~20mA output compatible for most control systems11.Magnetic Float Level Transmitter-FG SeriesPrinciple
The
“Magnet Float Level Indicator” is composed of the float and sensing rod
(shown as below). As the float raised or lowered by liquid level, the
sensing rod will have a resistance output, which is directly
proportional to the liquid level. Also, the float level indicator can be
equipped with the TAB-1531 (please see page 3) to produce a 0/4~20mA
signal. In addition, we can use with PB series bargraphic display
scaling panel meter for level control and display. Anyway, “Magnet Float
Level Indicator” is a great benefit to all kinds of industries with its
easy working principle and reliability.
Features
-
Every sensing element is protected by a plastic package, safety in use and transport.
-
High performance and reliability of electric circuit modular designed.
-
Lower installation costs, less maintenance, reduced personnel training, and decreased plant shock down time.12. By-Pass Level Transmitter-EF SeriesPrincipleBy
by-passing a liquid to the outside chamber, taking advantage of a float
inside the chamber with a magnet inserted as well as in the color
flags, one can reveal the level of the liquid in a tank as the flags
turn and change color by magnetic attraction to the float.Features
-
Applicable in environments with high temp., high pressure, strong acid, strong alkali and hazardous locations.
-
The structure is simple but durable and reliable. It is also with various optional devices for upgrade in use.
-
A Level Transducer or Magnetic Switches can be installed and adjusted with no need to stop any process.
-
It is not operated by electricity and with not be affected by power failure.
-
The flag display is scaled by a piece of color, division every 10cm, one can easily read the levels height.
-
Multiple
applications for textile dyeing, sewage water processing, power
generating, hot coal oil boiler and petrochemical industrie12. Mini By-Pass Level Transmitter-MEF Series
-
By
by-passing a liquid to the outside chamber, taking advantage of a float
inside the chamber with a magnet inserted as well as in the color
flags, one can reveal the level of the liquid in a tank as the flags
turn and change color by magnetic attraction to the float.Features
-
Applicable in environments with high temp., high pressure, strong acid, strong alkali and hazardous locations.
-
The structure is simple but durable and reliable. It is also with various optional devices for upgrade in use.
-
A Level Transducer or Magnetic Switches can be installed and adjusted with no need to stop any process.
-
It is not operated by electricity and with not be affected by power failure.
-
The flag display is scaled by a piece of color, division every 10cm, one can easily read the levels height.
-
Multiple
applications for textile dyeing, sewage water processing, power
generating, hot coal oil boiler and petrochemical industries.13. Ultrasonic Level Transmitter-EA Series
Principle
The
ultrasonic level Indicator is a low-cost, noncontact and
easy-to-install measurement device. It is able to meet the every-day
needs of commercial production, as well serving a more specialized role
in the technologically-advanced aero-space industry, thus placing it
firmly in the category of high-level measurement technology. Unlike
other level indicators with limited uses, the easy-to-install ultrasonic
level indicator is a highly-accurate device with enough specialized
uses to ensure that the needs of the customer are met.
Features
-
Measuring range is available with 2M, 5M, 7.5M, 10M,15M, 20M, 50M
-
Measuring accuracy +/-0.25% in liquid resolution is 2 mm.
-
Output : 2-wire, 3-wire and indicator (transducer and controller are separated).
-
Beam small angle, short blanking distance, is suitable for small tank.
-
Analog output : 4 ~20mA or 20 ~4mA.
-
Supply voltage: 110 / 220VAC or DC24V.
-
Suitable for powder and liquid application.
-
Fail-safe function, can accommodates the possibility of transducer or power failure.
-
Operating temperature: -20°C ~ 60°C. Enclosure rating: IP-65.
-
Communication port : RS232, RS485. Relay output : 1~5 x SPDT.14. FMCW Radar Level Transmitter-JFR Series
Principle
FMCW
radar adopts a high frequency signal, which is emitted via an antenna
and swipe frequency increment by 0.5GHz during the measurement,
reflected by the target surface and received at a time delay. The
frequency difference, which is calculated from the transmitting
frequency and the received frequency, which is directly proportional to
the measured distance (or material surface).
The frequency difference
then is processed by Fast Fourier Transformation (FFT) to identify the
signal in Intermedium Frequency (IF). This FMCW radar is innate with
signal / noise enhancement and filtering of echo-back via Phase-Lock
Loop (PLL) circuit that is the best solution for complex environment and
high accuracy measurement.
Features
-
Corrosive and toxic liquid, hydrocarbons, slurries
-
Not affected by specific gravity, pressure, temperature, viscosity, foam, and dust
-
5 digits LCM display
-
Indicate signal wave inside the silo.
-
Selection of Different Measurement unit(m, cm, mm, inch, ft, %, mA)
-
Measuring distance and actual level.
-
Language selection of traditional Chinese, simplified Chinese, English.
-
4-20mA/ 4 lead wires
-
Modbus RS-485 to enhance isolation and easy for remote control.
-
CE standards for isolation(EFT 2000V, B class or better)
-
Suitable for mid-range signal
-
4-20mA output
-
Set functions to the continuous measuring device via FAS software.
-
Isolated circuit design.
15. Rotary Paddle Level Switch-SE Series
PrincipleThe
SE series operating principle is simple. A unit is usually located
through a bin wall at the top, middle or low level of a bin. During
normal operation (no material present) a synchronous motor rotates the
paddle at 1 RPM. When this paddle rotation is impeded by material,
surrounding the paddle, motor will stall and cause the Micro-switch to change state. (indicating an alarm or control)Features-
Unique
sealing ring design, it can perform good dust protection to avoid the
dust permeate into housing body along with the shaft. -
The torque force is adjustable.
-
The performance of torsion is stable and reliable.
-
If the rotary paddle bears an extra overload, the motor will be appeared slide to prevent the inside mechanism damaged.
-
It
is rationally designed, the inside mechanisms are easily tore down for
checking, maintenance and replacement. It doesn”t necessary to remove
the complete set from the tank. -
Very suitable for small tank and material of low density16. Capacitance Level Switch-SA SeriesPrincipleThe
capacitance level sensor measuring principle is base on the ”
capacitance effects ” , when this level sensor is set on a silo, it will
be formed a condenser between the detector electrode and the silo wall.
The capacitance of this condenser varies proportional to the change of
material specific inductivity ( DK value) of the material stored in the
silo , when the more material substances increased in the silo, the more
capacitance value added simultaneously, then it will let his interior
circuit “s resonant signal to create a bigger amplitude ,and such a
signal amplitude become more or less than factory default threshold
value, the relay device will be energized.Features
-
No moving parts inside the device, it will be not affected by friction, which are suitable for powder or liquid application.
-
Various models are suitable for different application.
-
The sensitivity, which includes 10pf, 20pf and 40pf, is adjustable.
-
With timing delay design, timing adjustable range 0 ~ 6 seconds.
-
Voltage: 110V/220VacC or 24Vdc
-
Output: NPN transistor, 5A/250Vac and 5A/240Vac SPDT contact.
-
Standard connecting screw 1″ NPT, special specification are acceptable.
-
Enclosure protection IP65 or explosion-proof.
-
SA-75U Zener barriers inside provide intrinsic safety (Ex ia IIC) to SA17( )D type level switch.
-
-
Sturdy and durable design. No calibration needed.
-
Special design to avoid the accumulation of material on probe.
-
High / Low fail safe modes
-
Field-operatable in sensitivity adjustment to fit versatile density of material.
17.Vibrating Probe Level Switch-SC SeriesPrincipleThe
vibrating probe of level switch operated by using two piezoelectric
elements built-in on vibration tube. The first piezoelectric element
triggered by pulse signal that created from circuit to transport
vibration energy out, and the other piezoelectric element receives the
vibration and transmits it to output electric signal. While the probe
contacts material, the detection signal will be decayed and the
vibration will hold and send out the relay on.
Vibrating probe of
level switch provides reliable & maintenance-free for bulk solids.
Just a simple mounting and calibration procedure that keep your facility
in save and monitoring. This device can withstand fiercely lateral
loads and static electricity.
For friendly use, Fail-safe is equipped as standard to prevent malfunction caused by power shortage.
Features
-