Sage 200 Thermal Mass Flowmeter

The Sage 200 thermal flow meter is a cost-effective alternative to the Sage Prime which offers the same level of performance. The 200 is manufactured to accommodate our International customers. The flow meter measures gas mass flow and has the same accuracy, repeatability, low-end sensitivity, response time, turndown and resolution as the Prime without some premium features.

If the user needs to verify that the meter is in calibration, while still in the field and in the pipe, use the Sage Prime, which includes the award-winning Sage In-Situ Calibration Verification. Likewise, if a high-contrast graphical display is desired, the Prime will better serve your needs.

Features :
  • Approved for use in Class I Div 2 hazardous areas and CE approved
  • Available in 24 VDC or 115/230 VAC
  • Isolated 4-20 mA signal and pulsed output of total flow
  • Modbus RTU with RS-485 communication (optional)
  • Available with integral or remote electronics
  • For remote models, lead length compensation permits cable lengths up to 1000 feet
  • NEMA 4 and explosion-proof junction box
  • For use with a ½” insertion probe in 1″ and larger pipe or in the in-line flow body sizes 1/4″ to 4″
  • Available in blind configuration or display with window providing flow rate, total flow and gas temperature

Benefits
  • Measures mass flow.
  • Sage meters have the lowest rate of energy loss with a power dissipation of 2.5 watts, making them the most efficient thermal mass flow meter.
  • All units come calibrated from the Sage NIST traceable calibration facility and are preconfigured with the specified process and installation parameters for the application.
  • The meter has a two compartment compact housing with a separate wiring section containing large, easy to access terminals to simplify field installation.

Applications
  • Natural gas flow to burners
  • Compressed air flow measurement
  • Combustion air
Specifications


Performance
  • Accuracy: +/– 1% of reading plus 0.5% of full scale
  • Repeatability: 0.2% of reading
  • Low End Sensitivity: 5 SFPM (1 SCFM in 6″ pipe)
  • Response Time: 1 second time constant
  • Turndown: 100:1
  • Resolution: 1000:1
Electronics
  • Power: 24 +/-10% VDC or 90 – 265 VAC
  • Output: 4-20 mA
  • Pulse: 100 mA maximum
  • Isolated: External powered 4-20 and pulse
  • Modbus: RS 485 RTU optional
  • Ratings: Class I, Division 2, NEMA 4, CE
  • Ambient Temperature: –40 to 150° F (–40 to 65° C)
Sensor
  • Type: Insertion probe (1/2″ diameter), flow body (1/4″ to 4″)
  • Materials: 316 stainless steel and Hastelloy C
  • Process Temperature Range: –40 to 450°F (–40 to 230° C)
  • Process Pressure: Max 500 psig

Sage 300 Flowmeter Thermal Mass

Sage 300 Thermal Mass Flow Meter

The Sage 300 thermal mass flow meter is an economical alternative to the Sage Prime® while offering comparable performance. The meter measures gas mass flow and has the same accuracy, repeatability, low-end sensitivity, response time, turn down and resolution as the Prime without some premium features.

If the user needs to verify that the meter is in calibration, while still in the field and in the pipe, use the Sage Prime, which includes the award-winning Sage In-Situ Calibration Verification. Likewise, if a high-contrast graphical display is desired, the Prime will better serve your needs.
The 300 is manufactured to accommodate our customers in the United States and Canada .


Features

  • Available in 24 VDC or 115/230 VAC
  • Isolated 4-20 mA signal and pulsed output of total flow
  • Available with integral or remote electronics
  • For remote models, lead length compensation permits cable lengths up to 1000 feet
  • NEMA 4 and explosion-proof junction box
  • For use with a ½” insertion probe in 1″ and larger pipe or in the in-line flow body sizes 1/4″ to 4″
  • Available in blind configuration or display with window providing flow rate, total flow and gas temperature

Benefits

  • Measures mass flow.
  • Sage meters have the lowest rate of energy loss with a power dissipation of 2.5 watts, making them the most efficient thermal mass flow meter.
  • All units come calibrated from the Sage NIST traceable calibration facility and are preconfigured with the specified process and installation parameters for the application.
  • The meter has a two compartment compact housing with a separate wiring section containing large, easy to access terminals to simplify field installation.

Applications

  • Natural gas flow to burners
  • Compressed air flow measurement
  • Combustion air

Specifications


Performance

  • Accuracy: +/– 1% of reading plus 0.5% of full scale
  • Repeatability: 0.2% of reading
  • Low End Sensitivity: 5 SFPM (1 SCFM in 6″ pipe)
  • Response Time: 1 second time constant
  • Turndown: 100:1
  • Resolution: 1000:1

Electronics

  • Power: 24 +/-10% VDC or 90 – 265 VAC
  • Output: 4-20 mA
  • Pulse: 100 mA maximum
  • Isolated: External powered 4-20 and pulse
  • Modbus: RS 485 RTU optional
  • Ratings: Class I, Division 2, NEMA 4, CE
  • Ambient Temperature: –40 to 150° F (–40 to 65° C)

Sensor

  • Type: Insertion probe (1/2″ diameter), flow body (1/4″ to 4″)
  • Materials: 316 stainless steel and Hastelloy C
  • Process Temperature Range: –40 to 450°F (–40 to 230° C)
  • Process Pressure: Max 500 psig

Sage Flowmeter Integral Inline

SPECIFICATION :

STYLE  : Integral In-Line Mass Flow Meter
SENSOR: Two reference grade Platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION:
ELECTRONICS: Microprocessor based (Hybrid-Digital)
ELECTRONICS ENCLOSURE: Integral mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes – Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups , C, D T4 (24VDC);
CE (AC Power or 24VDC)
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C), Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC pulse for Totalized value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40° to 150°F (66°C)
FLOW BODY: 316SS Schedule 40 Flow Bodies sized from 1/4″ x 6″ long to 4″ x 12″ long.
Male NPT ends standard (Flanges and other options available)
RELAYS: N/A
FLOW CONDITIONING: Flow Conditioners are built in to In-Line Style Flow Bodies from 1/2″ to 4″


ENCLOSURE DEPTH: DC: 4.35″ ; AC: 5.35″

Sage Thermall Mass Flowmeter

Thermall Mass Gas Flow Meter

SPESIFICATION :

STYLE : Integral Insertion Mass Flow Meter
SENSOR: Two reference grade platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION:
ELECTRONICS: Microprocessor based (Hybrid-Digital)
ELECTRONICS ENCLOSURE: Integral mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes – Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups B, C, D T4 (24VDC);
CE (AC Power or 24VDC)          
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C),Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC Pulse for Totalized Value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40° to 150°F (66°C)
PROBE STYLE / LENGTH: 1/2″ OD Probe (3/4″ optional) Lengths 6″ to 36″
RELAYS: N/A
FLOW CONDITIONING: Captive Flow Conditioners available upon request with meter purchase
ENCLOSURE DEPTH: DC: 4.35″ ; AC: 5.35″

Sage Flowmeter

SPESIFICATION :

STYLE: Remote Insertion Mass Flow Meter
SENSOR: Two reference grade platinum RTD clad in 316SS sheath
MATERIAL: Wetted metal components: 316SS
POWER: 24VDC Standard (12VDC or 115/230VAC optional)
POWER DISSIPATION:
ELECTRONICS: Remote-Style Microprocessor based (Hybrid-Digital)
PROBE ENCLOSURE: Junction Box is Explosion Proof, Class I, Div 2, Groups B, C, D (no electronics)
TRANSMITTER ENCLOSURE: Remote mount, NEMA 4 enclosure
DISPLAY: High contrast photo-emissive OLED graphical display (Flow Rate, Totalizer, Temperature)
TURNDOWN: 100 to 1
RESOLUTION: 1000 to 1
LOW END SENSITIVITY: 5 SFPM
FIELD CALIBRATION CHECK: Yes – Digital system allows raw signal validation (milli-watts)
COMMUNICATIONS: Modbus® compliant RS485 RTU or optional HART® communications
APPROVALS: CSA C22.2 (24 VDC); ULI604, Class I, Div 2, Groups B, C, D T4 (24VDC);
CE (AC Power or 24VDC)
FIELD RECONFIGURABLE: Sage ADDRESSER required
FLOW ACCURACY: +/- 0.5% of Full Scale +/- 1% of reading (Enhanced accuracy optionally available with limited turn-down)
FLOW REPEATABILITY: 0.2%
RESPONSE TIME: 1 second time constant
GAS TEMPERATURE RANGE: Standard -40° to 200°F (93°C), Optional to 300°F (149°C) and 450°F (232°C)
GAS PRESSURE: 500 PSIG (If higher pressure needed, contact Sage)
FLOW OUTPUT: 4 to 20 mA for Rate
TOTALIZER: 24VDC pulse for Totalized value
TEMPERATURE OUTPUT: Through Modbus® only
AMBIENT TEMPERATURE: -40°F to 150°F (66°C)
PROBE STYLE / LENGTH: 1/2″ OD Probe (3/4″ optional) Lengths 6″ to 36″
RELAYS: N/A
CABLE LENGTH: 25′ Standard (max length 1000′)
FLOW CONDITIONING: Captive Flow Conditioners available upon request with meter purchase


TRANSMITTER ENCL DEPTH: DC: 4.35″ ; AC: 5.35″